Custom Search
Showing posts with label three phase analysis. Show all posts
Showing posts with label three phase analysis. Show all posts

Wednesday, July 16, 2008

Program for analysis of three phase circuit representing generator transmission line and load - PSPICE

The aim of the program is to analyze the three phase circuit representing generator transmission line and load and to plot 3 phase current and neutral current.

Problem:
220v,
50hz supply is applied to
a) balanced 3-phase star connected load contains 25 ohms of resistance and 6mH of inductance in each phase
b)
Un-balanced 3-phase star connected load of 10 ohms, 3mH inductance, 20ohms, 4mh & 30 ohms , 5mh inductance for 3-phase respectively. Plot 3 phase currents and neutral laod. If source L is 6mH and value of neutral inductance is 7mH


PROGRAM CODE ( for balanced 3-phase analysis )

*balanced 3-phase analysis
*source description
VS1 1 2 SIN(0 220 50HZ 0 0 0DEG)
VS2 1 4 SIN(0 220 50HZ 0 0 120DEG)
VS3 1 6 SIN(0 220 50HZ 0 0 240DEG)
VS4 10 9 DC 0V
VS5 10 11 DC 0V
VS6 10 13 DC 0V
VS7 0 10 DC 0V
*COMPONENT DESCRIPTION
L1 2 3 6M
L2 4 5 6M
L3 6 7 6M
L4 1 0 6M
L5 8 3 6M
L6 14 5 6M
L7 12 7 6M
R1 8 9 25
R2 12 11 25
R3 14 13 25
* ANALYSIS DESCRIPTION
.TRAN 20ms 160ms
*OUTPUT DESCRIPTION
.PROBE
.END
OUTPUT

Program for analysis of three phase circuit representing generator transmission line and balanced load

PROGRAM CODE ( for Un-balanced 3-phase analysis )

*unbalanced 3-phase analysis
*source description
VS1 1 2 SIN(0 220 50HZ 0 0 0DEG)
VS2 1 4 SIN(0 220 50HZ 0 0 120DEG)
VS3 1 6 SIN(0 220 50HZ 0 0 240DEG)
VS4 10 9 DC 0V
VS5 10 11 DC 0V
VS6 10 13 DC 0V
VS7 0 10 DC 0V
*COMPONENT DESCRIPTION
L1 2 3 6M
L2 4 5 6M
L3 6 7 6M
L4 1 0 6M
L5 8 3 3M
L6 14 5 4M
L7 12 7 5M
R1 8 9 10
R2 12 11 30
R3 14 13 20
* ANALYSIS DESCRIPTION
.TRAN 20ms 160ms
*OUTPUT DESCRIPTION
.PROBE
.END

OUTPUT Program for analysis of three phase circuit representing generator transmission line and unbalanced load